By the PEMCO Engineering Team, Lahore. Updated 21 November 2026.
Short answer
- If patients move between floors in their beds, the hospital needs a bed lift. The NHS guidance most designers use, HTM 08-02, sets it at 2500 kg, a 1800 x 2700 mm car and a 1400 mm door.
- A 1600 kg stretcher lift (1400 x 2400 mm car, 1400 mm door) takes a patient on a trolley or stretcher, or an empty bed. It is not built for a patient in bed with staff and equipment.
- In LDA areas, lifts are required in non-residential buildings on plots above 7 marla, and the owner signs a lifetime maintenance undertaking with the plans.
- Plan bed lifts in pairs and put them on the generator supply with an automatic rescue device. One lift serving the operating theatre is one breakdown away from a crisis.
In a hospital, the lift is the corridor between the emergency room, the operating theatre and the ward. A standard 8-person passenger lift will not take a hospital bed. If that is the only lift in the building, a patient after surgery has to leave the bed to change floors. This guide is for hospital owners, doctors building a clinic, and architects in Lahore who need to get the lifts right before the structure is designed.
Bed lift, stretcher lift or passenger lift
Pick the lift by what has to travel in it: a person, a trolley, or a full hospital bed with staff around it. We could not find a Pakistani hospital-specific lift standard, so most designers here work from the UK’s Health Technical Memorandum 08-02: Lifts (2016 edition). Its standard healthcare lifts are:
| Lift type | Rated load | Car (width x depth) | Clear door | What it carries |
|---|---|---|---|---|
| Bed lift | 2500 kg | 1800 x 2700 mm | 1400 mm | Patient on a standard extended bed, with staff and equipment |
| Trolley / stretcher lift | 1600 kg | 1400 x 2400 mm | 1400 mm | Patient on a trolley or stretcher, or an empty bed |
| General passenger lift | 1275 kg | 2000 x 1400 mm | 1100 mm | Visitors, staff, wheelchair users |
| Smaller passenger lift | 1000 kg | 1600 x 1400 mm | 1100 mm | Lower-traffic buildings, wheelchair plus one person |
| Goods lift | 2500 kg | 1800 x 2700 mm | 1800 mm | Supplies, waste, equipment |
The 2700 mm depth is not generous. HTM 08-02 shows a standard bed at roughly 2.4 m long once a pump is hung on its end, with space left for a nurse at the head and a drip stand or monitor at the side. A car that fits the bed but not the people is the wrong car.
The door matters as much as the car. A 1400 mm clear opening lets a bed go straight in without a three-point turn in the lobby. Narrow doors on a deep car are a common false saving.
What the rules in Lahore say
For any hospital or clinic on a plot above 7 marla in an LDA area, a lift is a legal requirement, not an option. The LDA Building and Zoning Regulations 2019 (amended to January 2020) treat hospitals, clinics, nursing homes, labs and scan centres as “health institutions”, and several clauses apply to them:
- Section 6.4.2: lifts must be provided in non-residential buildings on plots above 7 marla, must meet international safety standards, and their number should suit the building’s size, height and use.
- Section 5.2.3: non-residential buildings need a ramp at least 4 ft wide, no steeper than 1:6, and a toilet for disabled people. A multi-storey building without lifts must make every floor reachable by ramp.
- Section 8.1.17: the owner gives a stamp-paper undertaking, with the building plans, that a company will handle lifetime maintenance of the lifts and other services.
- Fire and environment: hospitals need a fire department certificate before completion and an EPA no-objection certificate with the plans. Health care buildings with more than 50 beds, or high-rise ones, must have sprinklers throughout.
On DHA Lahore commercial plots, lifts must also be certified under the Annex-E checklist in DHA’s Construction & Development Regulations, and the authority’s lift installation guidelines make backup power, an intercom and overload protection mandatory for plazas.
Separately, the Punjab Healthcare Commission licenses hospitals and clinics against its Minimum Service Delivery Standards. We did not find a lift size in the public summaries of those standards, which is why the sizes in this guide come from HTM 08-02. Ask your hospital planner what your licence category expects.
How many lifts a hospital needs
The honest minimum is two lifts that can each take a patient, because every lift stops for servicing and some stop without warning. HTM 08-02 says lifts should be provided at least in pairs wherever possible (paragraph 4.4), and calls a single operating-theatre lift inadvisable (paragraph 5.8).
- Small clinic or day-care centre (ground plus two or three floors): at least one stretcher or bed lift for patients, plus a passenger lift for visitors. If only one patient lift fits, keep beds, recovery and the theatre on floors that a ramp or the ground floor can serve.
- Hospital with wards upstairs: bed lifts in pairs, kept apart from visitor traffic, and a separate goods or service lift so waste and supplies do not share a car with patients.
- Larger hospitals: a traffic study. HTM 08-02 suggests estimating the building population as three times the number of beds, then checking peak demand at visiting hours.
Keep a bed-sized car among the lifts that can be used for evacuation. HTM 08-02 (paragraph 4.59) says that where in-patients may need to be evacuated, escape lifts should be bed-lift size.
Features that matter for patients
A hospital lift is judged by how gently it moves a patient who has just had surgery, and how reliably it does so at 3am. These are the points to write into the specification:
| Feature | What to ask for | Why |
|---|---|---|
| Smooth ride | Acceleration no more than 0.6 m/s², jerk no more than 1.0 m/s³ (HTM 6.24) | Post-operative and cardiac patients feel every jolt |
| Stopping accuracy | ±5 mm at every floor (HTM 6.25) | Bed wheels catch on a step at the door |
| Door dwell | 7 seconds for bed and trolley lifts (HTM 5.32) | Gives porters time to push a bed through |
| Priority control | A key switch that takes the car out of public service for a patient transfer | Stops visitors calling the lift away mid-transfer |
| Safety gear | No instantaneous safety gear on patient lifts (HTM 6.90) | A sudden stop can injure a patient on a bed |
| Finishes | Stainless steel, recessed handrails, bump rails at bed height | Easy to clean; beds and trolleys hit the walls |
| Shaft hygiene | Shaft walls dust-sealed and painted (HTM 6.74) | A shaft runs through every floor and spreads dust |
| Spares | Written commitment on parts availability; HTM expects 20 years | A lift waiting for an imported board is a lift out of service |
A car with doors on two opposite sides (a through car) helps on tight sites: the bed rolls in from the emergency side and out towards the theatre without turning. It needs a bigger shaft, so decide early.

Planning a hospital or clinic?
WhatsApp us your floor plans, number of beds and which floors have wards and theatres. Our engineers will suggest the number and size of lifts and the shaft to design around. Free site survey in Lahore and nearby areas, video consultation anywhere in Punjab.
Traction or hydraulic in Lahore’s heat
For most hospitals above three or four floors, a traction lift with a variable-frequency (VVVF) drive is the sensible choice. Hydraulic suits low buildings, but only with a cooled pump room.
Hydraulic bed lifts carry heavy loads smoothly and lower the car by gravity, which makes manual rescue simple. HTM 08-02 limits them to about 18 m of travel and advises against them where the lift makes more than 45 up-starts an hour or runs faster than 0.8 m/s. A busy hospital lift can exceed that start count at visiting hours.
Heat is the Lahore-specific problem. HTM 08-02 keeps machine rooms between 5 °C and 40 °C and hydraulic pump rooms between 15 °C and 35 °C. A closed rooftop room in a Lahore June is well above that, and the oil and electronics suffer. Whichever drive you choose, budget for cooling the machine room or controller space, and vent the heat outside, not back into the room.
Machine-room-less (MRL) lifts save roof space, but the controller often sits in a cabinet on a landing. In a hospital corridor that means barriers around a technician working beside patient traffic, and DHA Lahore requires prior approval for MRL lifts. Our guide to passenger lifts for plazas and apartments in Lahore compares the three drive types in more detail.
Load-shedding and backup power
A hospital bed lift must keep working when LESCO’s supply goes, and must never leave a patient stuck between floors. That takes two separate things.
1. An automatic rescue device on every lift
An automatic rescue device (ARD, also called ELD) runs on batteries. When the supply fails, it moves the car to the nearest floor and opens the doors. In a hospital the battery must be load-tested on every service visit, because Lahore heat shortens its life and it only matters on the day it is needed.
2. Patient lifts on the essential supply
At least one bed lift, and any lift used for evacuation, should run from the generator through an automatic changeover. HTM 08-02 asks that the backup supply has the same characteristics as the main supply. In practice, that means a generator sized for the lift motor’s starting current as well as the theatre, ICU and lighting loads it shares. Bed lifts normally need a three-phase supply, so check the sanctioned load with LESCO early.
Solar helps, but it is not lift backup. Many Lahore hospitals now run rooftop solar to cut daytime bills. A grid-tied system switches off when the grid fails, so the generator and the ARD remain the lift’s real backup. See our solar installation in Lahore page for hybrid options.
Clinics in converted buildings
A bed lift needs a large shaft, and many Lahore clinics are in converted houses or narrow commercial plots. A 1800 x 2700 mm car needs a shaft well beyond those dimensions, plus a pit below the lowest floor and headroom above the top one. The exact sizes come from the supplier’s drawing for the chosen model, so get that drawing before any slab is cut.
Adding a shaft to an existing building means cutting slabs, adding beams around the opening and, in LDA areas, an addition and alteration plan. Our guide to adding a lift to an existing building walks through the structure, shaft locations and approvals.
If the building simply cannot take a bed lift, be honest about it. A 1600 kg stretcher lift still moves a patient on a trolley. Then plan the building around that limit: keep inpatient beds, recovery and the operating theatre on the floors patients can reach without leaving their beds.
Checklist before you sign a quote
Ask every supplier, including us, to answer these in writing:
- Car and door size: clear internal car size and clear door opening, not the shaft size.
- Standard: which safety standard the lift meets (for example the EN 81 series), and the origin of the machine, controller and doors.
- Ride figures: acceleration, stopping accuracy and door dwell time, set for hospital use.
- Controls: priority or hospital service key, intercom, overload sensor, ARD.
- Power: motor rating and starting current, for the generator designer.
- Civil work and cooling: what is included for the shaft, pit, machine room and its ventilation.
- Maintenance: who services it, how fast they respond when a patient is trapped, and which spare parts are stocked in Lahore. Our guide to lift maintenance contracts in Lahore lists the clauses to check.
If your project is outside Lahore, our page on lift installation in Islamabad covers the rules there.
Frequently asked questions
What size is a hospital bed lift?
The UK’s HTM 08-02 guidance, widely used by designers, sets a bed lift at 2500 kg rated load with a clear car of 1800 x 2700 mm and a clear door opening of 1400 mm. That fits a patient on a standard extended bed with staff and equipment.
Is a 1600 kg lift enough for a hospital?
A 1600 kg trolley or stretcher lift (1400 x 2400 mm car, 1400 mm door) carries a patient on a trolley or stretcher, or an empty bed. It suits small clinics and day-care centres, but a hospital that moves patients in their beds needs a 2500 kg bed lift.
Is a lift mandatory for a hospital or clinic in Lahore?
In LDA areas, section 6.4.2 of the LDA Building and Zoning Regulations 2019 requires lifts in non-residential buildings on plots above 7 marla. Where a multi-storey building has no lift, every floor must be reachable by a ramp under section 5.2.3.
How many bed lifts does a hospital need?
At least two lifts that can take a patient, so one can be serviced or break down without cutting off wards or theatres. HTM 08-02 recommends lifts in pairs and calls a single operating-theatre lift inadvisable. Larger hospitals need a traffic study.
What happens to a hospital lift during load-shedding?
An automatic rescue device brings the car to the nearest floor and opens the doors. To keep at least one bed lift running, connect it to the generator through an automatic changeover, with the generator sized for the lift motor’s starting current.
Talk to an engineer about your hospital or clinic
PEMCO Engineering has installed home lifts, passenger lifts and cargo lifts in houses, commercial buildings and factories across Punjab. See our elevator and lift installation service. Call or WhatsApp 0322 4773987, or use the contact form for a free consultation.
Written by the PEMCO Engineering Team. Checked on 21 November 2026 against Health Technical Memorandum 08-02: Lifts (2016 edition, NHS England), the LDA Building and Zoning Regulations 2019 (amended to January 2020), DHA Lahore’s regulations and lift guidelines, and the Punjab Healthcare Commission’s published information. General guidance only; your hospital planner, approving authority and chosen lift supplier decide the final design.