Passenger Lifts for Plazas and Apartments in Lahore: Rules, Sizing and Backup

  • Post published:

By the PEMCO Engineering Team, Lahore. Updated 19 November 2026.

Short answer

  • The LDA Building and Zoning Regulations 2019 require lifts in non-residential buildings on plots above 7 marla. In DHA Lahore, every plaza lift must pass the Annex-E checklist.
  • Size lifts by traffic, not habit: ISO 8100-32 targets 6% of residents moved in five minutes, with lifts arriving at least every 60 seconds.
  • Most apartment blocks of 8 to 10 floors need two lifts: one carries the people, but the wait is too long and a breakdown leaves only the stairs.
  • Buildings 30 m (100 ft) or taller also need a fire lift.

A passenger lift in a plaza or apartment block is not a bigger home lift. It runs hundreds of trips a day, carries strangers, must pass inspection and has to cope with load-shedding. This guide is for owners, builders and residents’ committees in Lahore deciding what to install and what to check before signing a quote.

When a lift is required in Lahore

For most commercial buildings in Lahore, a lift is a legal requirement. The rulebook depends on where the plot is.

LDA-controlled areas

Section 6.4.2 of the LDA Building and Zoning Regulations 2019 (with amendments to January 2020) says lifts shall be provided in buildings other than residential on plots above 7 marla. They must meet international safety standards, and their number should suit the building’s size, height and use.

Section 8.1.17 is easy to miss: with the building plans you give a stamp-paper undertaking that a company will handle lifetime maintenance of the lifts, escalators and other services.

DHA Lahore

DHA’s Construction & Development Regulations (April 2026 edition) set out several rules for commercial buildings:

  • Regulation 39(f): on commercial plots over 3 kanal with a double basement or more than 3 floors, a lift or escalator from the parking basement to all floors is mandatory.
  • Regulation 33(b): the lift machine room on a commercial building can be at most 75 sq ft, within the height limit of 88 or 92 feet from road level.
  • Regulation 27(a): elevators in residential and commercial buildings must be validated and certified under Annex-E, and compliance is mandatory.

DHA’s lift installation guidelines list 20 mandatory items for a plaza, including three that are optional in houses: an emergency intercom, overload protection and emergency instructions inside the cabin. Others include ELD/UPS backup, door interlocks, a speed governor, pit buffers, machine room ventilation, a stability certificate and a preventive maintenance contract with a log book.

Tall buildings: the fire lift

Section 10.22 of the Building Code of Pakistan, Fire Safety Provisions 2016 requires fire lifts in buildings 30 m (100 ft) or taller. Each must carry at least 8 passengers, have a ground-level emergency switch and an intercom to the control room, and be run only by firefighters during a fire. The code also says lifts do not count as exits, so the stairs must work on their own.

Private societies such as Bahria Town have their own building control rules. Get them before the structure is designed.

How many lifts, and how big

The right number of lifts comes from a simple traffic check: how many people need to move in the busiest five minutes, and how long they will wait. The international standard for this, ISO 8100-32, gives these design targets, as summarised by Elevator World:

BuildingPeople moved in 5 minutesInterval between lifts
Apartments / residential6% of the population60 seconds or less
Offices12% of the population30 seconds or less
ISO 8100-32 up-peak targets. Shopping plazas need a full traffic study.

A worked example: a 10-storey apartment block

Take a ground-plus-nine block with 4 flats on each upper floor: 36 flats, about 180 people at 5 per flat. The lifts need to move about 11 people in five minutes at the morning peak.

Our rough calculation for one 8-person lift at 1 m/s with 3.2 m floors gives a round trip of just over two minutes. It moves about 15 people in five minutes, which passes, but the interval is about two minutes, double the target. Add a second lift and the interval drops to about one minute, and the building keeps a working lift when one is being serviced or breaks down. That second reason matters most in practice.

Treat this as an illustration: real figures depend on floor heights, speed and doors. Every quote for a multi-storey building should include a proper traffic calculation.

Cabin size: plan for wheelchairs and furniture

The European accessibility standard EN 81-70 sets minimum car sizes, listed by KONE:

Car typeMinimum car (width x depth)Door openingWorks for
Type 11000 x 1300 mm800 mmWheelchair user alone
Type 21100 x 1400 mm900 mmWheelchair plus companion; sensible apartment minimum
Type 31100 x 2100 mm900 mmWheelchair plus others; furniture, stretchers
EN 81-70 minimum car dimensions.

Residents also move sofas, fridges and, in an emergency, a patient on a stretcher. With only one lift, a deeper car is worth the shaft space. Hospitals and clinics need more than that: see our guide to hospital bed lifts in Lahore for bed and stretcher lift sizes.

Traction, MRL or hydraulic

For most plazas and apartment blocks in Lahore, a traction lift is the default; hydraulic only makes sense for low buildings.

TypeSuitsStrengthsTrade-offs
Traction with machine roomMid- and high-rise plazas and apartmentsEasy maintenance access; provenNeeds a roof machine room (max 75 sq ft in DHA) that must be ventilated
Machine-room-less (MRL) tractionBuildings where roof space or height is tightSaves the roof room; efficient gearless motorsHarder service access; needs DHA prior approval
HydraulicLow buildings with a few stops, heavy loadsSmooth; load goes into the pit, not the roofSlow; more power per trip; oil and pump room
General guide only.

Lahore summers are hard on machine rooms: a closed rooftop room with a motor and controller gets far hotter than outside, and electronics fail early. DHA lists machine room ventilation (AC or fan) as mandatory. Budget for it.

Stainless steel lift landing doors with a call button panel
Illustration: stainless steel landing doors stand up to heavy daily use in plazas.

Planning lifts for a plaza or apartment block?

WhatsApp us your plans or floor count and building use. Our engineers will suggest the number, size and type of lifts and the shaft size to design around. Free site survey in Lahore and nearby areas, video consultation anywhere in Punjab.

Load-shedding, power and backup

In Pakistan, the backup plan is part of the lift, not an afterthought. There are two separate jobs to solve.

1. Getting people out when power fails

An automatic rescue device (ARD, also called ELD) runs on batteries. When the supply drops, it moves the cabin slowly to the nearest floor and opens the doors. DHA lists ELD/UPS backup as mandatory for both houses and plazas (see lift backup during load-shedding for how ARD, UPS and generator backup differ). Without it, every power cut in a busy plaza can mean someone trapped in the dark. It happens: rescuers had to free eight people, including women and children, from a stuck lift in a plaza on MM Alam Road, as Samaa reported.

2. Keeping the lift running

An ARD only finishes the trip. To keep lifts in service, the building needs a generator sized for the motors’ starting current, not just their running load. In DHA, generators are allowed only as standby, with commercial capacity capped by plot size (Regulation 58).

Passenger traction lifts normally need a three-phase supply. Make sure the building’s sanctioned load with LESCO covers the lifts, and apply early if it doesn’t.

Plaza vs apartment: what changes

A plaza and an apartment block can use the same lift model, but they wear it out differently.

  • Plazas get goods traffic. Without a service lift, shopkeepers move stock in the passenger lift, which means dented panels and door faults. Add a goods lift or specify hard-wearing finishes.
  • Plazas carry strangers. That is why DHA makes the intercom, overload protection and emergency instructions compulsory there.
  • Apartments run long hours. Quiet doors and a smooth ride matter more than top speed.
  • Apartments need clear ownership. Decide who pays for maintenance, holds the emergency key and calls for repairs; our guide to lift repair in Lahore explains what to do when a lift stops.

Questions to ask any lift company

Comparing quotes on price alone is how buildings end up with lifts that stop every month. Ask every supplier, including us:

  • Which safety standard does it meet? Get it in writing (for example the EN 81 series), with the origin of the machine, controller and doors.
  • Did you do a traffic calculation? A quote for a multi-storey building without one is a guess.
  • What is included? ARD, intercom, overload sensor, machine room ventilation and civil work are often priced separately. Check against DHA’s checklist line by line.
  • Which spare parts are stocked in Lahore? A lift waiting weeks for an imported board is out of service for weeks.
  • Who maintains it, and how fast do they respond? Get the maintenance terms, log book and breakdown response time in writing before you sign.

Mistakes we see on site

  • The shaft is built before the lift is chosen. Shaft width, depth, pit and headroom must come from the lift maker’s drawing. A shaft that is a few inches short or out of plumb forces a smaller car or costly breaking.
  • No pit waterproofing. Monsoon water collects in the pit and rusts buffers and wiring.
  • One lift for a tall block. Cheap at handover, painful every service day.
  • Generator not sized for the lift. It trips on start-up during load-shedding.
  • No maintenance contract after handover. DHA requires one, and lifts without regular service fail early. Our guide to lift maintenance contracts in Lahore explains what a good one should include.

For houses rather than commercial buildings, see our guides to a lift for home in Pakistan and adding a lift to an existing house. If your building is in Islamabad or Rawalpindi, our page on lift installation in Islamabad covers the DHA Islamabad rules for commercial buildings.

Frequently asked questions

Is a lift mandatory for a plaza in Lahore?

In LDA areas, yes for non-residential buildings on plots above 7 marla (LDA Building and Zoning Regulations 2019). In DHA Lahore, commercial plots over 3 kanal with more than 3 floors or a double basement need a lift or escalator to all floors, and every lift must pass DHA’s Annex-E checklist.

How many lifts does an apartment building need?

ISO 8100-32 suggests residential lifts move about 6% of residents in five minutes with an interval of 60 seconds or less. For a typical ground-plus-nine block, one 8-person lift carries the people but the wait is too long, so two lifts are usually right.

What cabin size should a passenger lift have?

Under EN 81-70, a car of at least 1100 x 1400 mm with a 900 mm door fits a wheelchair user and a companion, a sensible minimum for apartments. A deeper 1100 x 2100 mm car handles furniture and stretchers better.

Do passenger lifts work during load-shedding?

An automatic rescue device (ARD/ELD) brings the cabin to the nearest floor and opens the doors; DHA makes it mandatory. To keep lifts running, the building also needs a standby generator sized for the motors’ starting current.

When does a building need a fire lift?

The Building Code of Pakistan Fire Safety Provisions 2016 require fire lifts in buildings 30 m (100 ft) or taller, with room for at least 8 passengers, a ground-floor emergency switch and an intercom to the control room.

Talk to an engineer about your building

PEMCO Engineering has installed home lifts, passenger lifts and cargo lifts in houses, commercial buildings and factories across Punjab. See our elevator and lift installation service. Call or WhatsApp 0322 4773987, or use the contact form for a free consultation.

Written by the PEMCO Engineering Team. Rules checked on 19 November 2026 against the LDA Building and Zoning Regulations 2019, DHA Lahore’s regulations (April 2026) and lift guidelines, and the Building Code of Pakistan Fire Safety Provisions 2016. The traffic example is a simplified estimate; every building needs its own calculation and approved design.